Give step-by-step solution with explanation and final answer: 3 A 5,000kVA, 3 - phase transformer, 6.6/33kV, Delta/star has no load loss of 15kW and a full -load loss of 50kW. The impedance drop at full load is 7%. Calculate the primary voltage when a load of 3200kW at 0.8pf is delivered at 33kV.

Question:

Give step-by-step solution with explanation and final answer: 3 A 5,000kVA, 3 - phase transformer, 6.6/33kV, Delta/star has no load loss of 15kW and a full -load loss of 50kW. The impedance drop at full load is 7%. Calculate the primary voltage when a load of 3200kW at 0.8pf is delivered at 33kV.

This is AI generated Response.
Asked by: mayank
Created at: 2025-09-19 03:54:09

Final Answer:

Rendered Raw Text
Did you like this answer?
# Step-by-Step Solution Given: - **Transformer Rating**: 5000 kVA, 3-phase - **Voltage**: 6.6 kV (primary, delta), 33 kV (secondary, star) - **No load loss**: 15 kW - **Full-load loss (Total loss)**: 50 kW - **Impedance drop at full load**: 7% - **Load delivered**: 3200 kW at 0.8 pf (power factor), at 33 kV (secondary side) We are asked to **calculate the primary voltage** (at the 6.6 kV side) under these load conditions. --- ## 1. **Calculate Full-Load Current on Secondary Side** \[ \text{Full-load kVA} = 5000\, \text{kVA} \] \[ I_{FL,2} = \frac{\text{Full-load kVA} \times 1000}{\sqrt{3} \times V_{2}} = \frac{5000 \times 1000}{\sqrt{3} \times 33000} = \frac{5000000}{57154} \approx 87.45\, \text{A} \] --- ## 2. **Calculate Actual Load Current on Secondary Side** \[ \text{Load delivered} = 3200\, \text{kW} \text{ at } 0.8\, \text{pf} \] \[ S_{\text{load}} = \frac{3200\, \text{kW}}{0.8} = 4000\, \text{kVA} \] \[ I_{2} = \frac{4000 \times 1000}{\sqrt{3} \times 33000} = \frac{4000000}{57154} \approx 70.0\, \text{A} \] --- ## 3. **Determine Per-Unit Load Fraction** \[ \text{Load fraction} = \frac{70.0}{87.45} \approx 0.80 \] --- ## 4. **Calculate Load Loss at Actual Load** Load losses (mainly copper losses) vary as the square of the load: \[ \text{Load loss at actual load} = (\text{full load loss} - \text{no-load loss}) \times (\text{Load fraction})^2 \] \[ = (50 - 15)\,\text{kW} \times (0.80)^2 = 35 \times 0.64 = 22.4\, \text{kW} \] Total loss at this load: \[ \text{Total loss} = \text{no-load loss} + \text{load loss at actual load} = 15 + 22.4 = 37.4\, \text{kW} \] --- ## 5. **Calculate Output and Input Power** \[ \text{Output (delivered)} = 3200\, \text{kW} \] \[ \text{Input} = \text{Output} + \text{Losses} = 3200 + 37.4 = 3237.4\, \text{kW} \] --- ## 6. **Impedance Drop at Actual Load** Impedance drop at full load is **7%** (of rated voltage), at 0.8 power factor. Let’s calculate the **impedance voltage drop** at 0.8 per-unit load. Impedance drop (in percent) at a given load: \[ \text{Voltage drop} = \text{Percentage drop at full load} \times \text{Load fraction} \] \[ = 7\% \times 0.8 = 5.6\% \] But since impedance drop is a vector sum of resistive and reactive drops, and power factor affects it, let's be precise. If \( Z_{pu} = 0.07 \) per unit at full load, the voltage drop at less than full load and any power factor is: \[ \Delta V = I_2 \left[ R\cos\phi + X\sin\phi \right] \] But typically, with only percent impedance given, we use: \[ \text{Voltage drop (\%)} = \text{Impedance \%} \times \text{Load fraction} \times (\cos\theta) \] But for more accuracy, let's split impedance into resistance and reactance. Let \( x \) = reactance percent, \( r \) = resistance percent At full load, total losses are: - No-load loss = Iron loss = 15 kW - Full-load loss = 50 kW (includes iron + copper loss) - So, copper loss at full load = 50 - 15 = 35 kW The per-unit resistance drop at full load: \[ \text{Full-load copper loss} = 3 I_{FL,1}^2 R_{phase} \] But with percent impedance (Z%), and knowing the copper loss, we can use: \[ \text{Impedance (Z)}^2 = R_{pu}^2 + X_{pu}^2 \] And: \[ \text{Copper loss at full load} = I_{FL}^2 R \] Let’s find \( R_{pu} \): \[ \text{Per-phase full-load current} = 87.45\, \text{A} \] \[ \text{Per-phase voltage (secondary)} = \frac{33000}{\sqrt{3}} = 19052\, \text{V} \] \[ \text{Base power per phase} = \frac{5000}{3} = 1666.67\, \text{kVA} \] \[ \text{Base impedance (secondary)} = \frac{(19052)^2}{1666667} \approx 0.218\, \Omega \] \[ \text{Copper loss at full load} = 35\, \text{kW} \] \[ \text{Total copper loss} = 3 \times I_{FL}^2 \times R_{phase} \] \[ R_{phase} = \frac{35000}{3 \times (87.45)^2} = \frac{35000}{3 \times 7647.4} = \frac{35000}{22942.2} \approx 1.526\, \Omega \] \[ R_{pu} = \frac{1.526}{0.218} \approx 7.0 \] But this is 7 per unit, which is too high; let's use % base: \[ \text{Base MVA} = 5\, \text{MVA} \] \[ \text{Base voltage} = 33\, \text{kV} \] \[ \text{Base impedance} = \frac{33^2}{5} = 217.8\, \Omega \] But that's for single-phase. For three-phase, \[ Z_{base} = \frac{V_{LL}^2}{S_{base}} \] \[ = \frac{(33,000)^2}{5,000,000} = \frac{1,089,000,000}{5,000,000} = 217.8\, \Omega \] So, \[ R_{pu} = \frac{1.526}{217.8} = 0.007 \text{ (or 0.7\% per unit)} \] So, \[ Z_{pu} = 0.07 \text{ (7\%)} \] \[ R_{pu} = 0.007 \text{ (0.7\%)} \] \[ X_{pu} = \sqrt{(0.07)^2 - (0.007)^2} = \sqrt{0.0049 - 0.000049} = \sqrt{0.004851} \approx 0.0696 \text{ (6.96\%)} \] --- ## 7. **Voltage Drop at Actual Load and 0.8 pf** For any power factor, the per-unit voltage drop: \[ \Delta V_{pu} = (\text{Load fraction}) \times [R_{pu} \cos\phi + X_{pu} \sin\phi] \] Given: - Load fraction: 0.8 - \(\cos\phi = 0.8\) - \(\sin\phi = 0.6\) - \(R_{pu} = 0.007\) - \(X_{pu} = 0.0696\) \[ \Delta V_{pu} = 0.8 [0.007 \times 0.8 + 0.0696 \times 0.6] = 0.8 [0.0056 + 0.0418] = 0.8 \times 0.0474 = 0.0379 \] So, in percent: \[ \Delta V = 0.0379 \times 100 = 3.79\% \] --- ## 8. **Calculate the Primary Voltage Required** The transformer is delivering 33 kV (secondary, line-to-line) at the load terminals, which is after the voltage drop. The **primary voltage must be such that after accounting for this drop, the secondary voltage is 33 kV**. Let \( V_{2} \) = 33,000 V (at load), \( V_{1}' \) = ideal primary voltage required. The total actual secondary voltage at transformer terminals: \[ V_{2, \text{tr}} = V_{2} + \Delta V \] But since voltage drop is a percent of rated voltage, \[ \Delta V = 3.79\% \text{ of } 33,000 = 0.0379 \times 33,000 = 1,250\, \text{V} \] So, the transformer **secondary winding** must supply: \[ V_{2, \text{tr}} = 33,000 + 1,250 = 34,250\, \text{V} \] To maintain 33,000 V at the load, transformer secondary must be at 34,250 V. The transformer is ideal, so the ratio holds: \[ \frac{V_1}{V_2} = \frac{6,600}{33,000} = 0.2 \] So, \[ V_1 = V_2 \times 0.2 \] But since the transformer must supply 34,250 V at the secondary, the primary voltage must be: \[ V_{1, \text{required}} = 34,250 \times 0.2 = 6,850\, \text{V} \] --- ## 9. **Final Answer** ### **The required primary voltage is:** \[ \boxed{6,850\, \text{V}} \] --- ## **Summary Table** | Quantity | Value | |--------------------------|---------------------------| | Load delivered | 3,200 kW @ 0.8 pf | | Secondary voltage (load) | 33,000 V | | Load current (secondary) | 70.0 A | | Load fraction | 0.8 | | Voltage drop (secondary) | 1,250 V | | Secondary voltage (tr) | 34,250 V | | Required primary voltage | 6,850 V | --- ## **Answer** > **The required primary (6.6 kV side) voltage to maintain 33 kV at the secondary load terminals when supplying 3,200 kW at 0.8 pf is** > > \[ > \boxed{6,850\, \text{V}} > \] > > (rounded to the nearest 10 V)

📢 Instructions:

  • Ask anything relatd to above question only.
  • For new Question goto :

Study Help, Fast Answers

VIPSolutions focuses on clear, step‑by‑step explanations so you can learn quickly. Whether you need an AI‑generated walkthrough or a short hint to get unstuck, each solution is organized for fast reading and easy review later.

Search similar questions, compare approaches, and bookmark the best answers for revision. Our goal is simple: quick, reliable study help that feels natural—not noisy.