Give step-by-step solution with explanation and final answer: phase transmission line has an impedance per phase of ( 1 + j 3 ) ohms, supplies at load of 2 0 MW at unity power factor. What is the sending - end voltage of the efficiency is 9 2 % . A short 3 - phase transmission has an impedance per phase of ( 5 + j 1 0 ) ohms. The input voltage between lines is 1 2 . 8 kV and at the receiving end the load takes 1 , 2 0 0 kW and 6 0 Amp at a lagging power factor. What is the load voltage between lines? A 3 - phase transmission line 1 0 km long delivers 2 , 5 0 0 kVA at 6 0 0 volts. The power factor of the load is 0 . 8 0 lagging. If the impedance of each load is ( 0 . 3 + j 0 . 4 ) ohm / km , the sending end voltage between lines is nearest to a . 8 , 0 2 1 V b . 8 , 2 1 0 V c . 8 , 2 0 1 V A 3 3 - kV , 3 - phase transmission line has an impedance of ( 1 . 2 + j 1 ) ohm / phase . The load is 1 0 , 0 0 0 kVA at 0 . 8 lagging power factor. If the receiving send voltage line is 3 3 kV , the percent regulation of the line is ? a . 4 . 6 6 % b . 3 . 6 6 % c . 8 . 6 6 % d . 2 . 6 6 %

Question:

Give step-by-step solution with explanation and final answer: phase transmission line has an impedance per phase of ( 1 + j 3 ) ohms, supplies at load of 2 0 MW at unity power factor. What is the sending - end voltage of the efficiency is 9 2 % . A short 3 - phase transmission has an impedance per phase of ( 5 + j 1 0 ) ohms. The input voltage between lines is 1 2 . 8 kV and at the receiving end the load takes 1 , 2 0 0 kW and 6 0 Amp at a lagging power factor. What is the load voltage between lines? A 3 - phase transmission line 1 0 km long delivers 2 , 5 0 0 kVA at 6 0 0 volts. The power factor of the load is 0 . 8 0 lagging. If the impedance of each load is ( 0 . 3 + j 0 . 4 ) ohm / km , the sending end voltage between lines is nearest to a . 8 , 0 2 1 V b . 8 , 2 1 0 V c . 8 , 2 0 1 V A 3 3 - kV , 3 - phase transmission line has an impedance of ( 1 . 2 + j 1 ) ohm / phase . The load is 1 0 , 0 0 0 kVA at 0 . 8 lagging power factor. If the receiving send voltage line is 3 3 kV , the percent regulation of the line is ? a . 4 . 6 6 % b . 3 . 6 6 % c . 8 . 6 6 % d . 2 . 6 6 %

This is AI generated Response.
Asked by: Test User 100308
Created at: 2025-05-21 06:06:09

Final Answer:

Rendered Raw Text
Did you like this answer?
Let's solve each problem step by step: --- ### 1. **Sending-End Voltage for 3-phase Line** #### **Given:** - **Load:** 20 MW (20,000 kW) at unity power factor - **Impedance per phase:** \( Z = 1 + j3 \,\Omega \) - **Efficiency:** 92% #### **To Find:** Sending-end voltage --- #### **Step 1: Calculate Receiving End Power and Current** - Since efficiency \( \eta = 92\% \): \[ \eta = \frac{P_{R}}{P_S} \] \[ P_S = \frac{P_{R}}{\eta} \] So, \[ P_S = \frac{20,000\,kW}{0.92} = 21,739.13\,kW \] #### **Step 2: Find Receiving End Line-to-Line Voltage** - Not given directly. Let's denote it as \( V_{R} \). - Since power factor is unity, \( \cos\phi = 1 \). - For 3-phase: \[ P_{R} = \sqrt{3} V_{R} I_{R} \cos\phi \] \[ 20,000 = \sqrt{3} V_{R} I_{R} \] (All in kW, so voltage in kV.) #### **Step 3: Express Current in Terms of Voltage** \[ I_{R} = \frac{20,000}{\sqrt{3} V_{R}} \] #### **Step 4: Calculate Voltage Drop Across Line** - Per phase drop: \[ \Delta V_{\text{ph}} = I_{R} Z = I_{R} (1 + j3) \] - Since unity p.f., current is in phase with voltage. #### **Step 5: Find Sending-End Voltage** \[ V_{S,ph} = V_{R,ph} + \Delta V_{\text{ph}} \] \[ V_{S,ph} = V_{R,ph} + I_{R} (1 + j3) \] - But we need either \( V_{R} \) or \( I_{R} \) to proceed. Since not specified, this problem is **missing the receiving end voltage** (or current), and can't proceed numerically without it. --- ### 2. **Short 3-phase Transmission Line** #### **Given:** - **Line impedance per phase:** \( Z = 5 + j10\,\Omega \) - **Sending-end (input) line voltage:** \( V_S = 12.8\,kV \) - **Receiving-end load:** 1200 kW, 60 A at lagging p.f. #### **To Find:** Load voltage between lines (\( V_R \)). --- #### **Step 1: Calculate Power Factor** - Power = \( \sqrt{3} V_R I_R \cos\phi \) - \( I_R = 60\,A \) - \( P = 1200\,kW \) \[ \cos\phi = \frac{P}{\sqrt{3} V_R I_R} \] But \( V_R \) is unknown. #### **Step 2: Find Per-phase Load Voltage** - For star connection: \[ V_{R,ph} = \frac{V_R}{\sqrt{3}} \] - Load current is 60 A per phase. #### **Step 3: Calculate Power Factor:** \[ 1200\times 10^3 = \sqrt{3} V_R \times 60 \times \cos\phi \] \[ V_R \cos\phi = \frac{1200 \times 10^3}{\sqrt{3} \times 60} \] \[ V_R \cos\phi = \frac{1200000}{103.923} = 11,546\,V \] But \( V_R \) and \( \cos\phi \) are multiplied. We need one to find the other. Let's try another way: we know current, so total apparent power: \[ S = \sqrt{3} V_R I_R \] \[ |S| = \sqrt{P^2 + Q^2} \] But not enough info to solve directly unless we assume p.f. (which is not given numerically). **If we assume p.f. = 0.8 lagging (common for such problems):** \[ \cos\phi = 0.8 \] \[ V_R = \frac{1200\times 10^3}{\sqrt{3}\times 60 \times 0.8} \] \[ V_R = \frac{1200000}{83.138} = 14,438\,V \] But sending-end is only 12.8 kV, so this can't be. We need more information (probably missing p.f. value). --- ### 3. **Transmission line, Find Sending-end Voltage** **Given:** - Length = 10 km - Load = 2500 kVA at 600 V, p.f. = 0.8 lagging - Impedance per km per phase: \( Z = 0.3 + j0.4\,\Omega \) - To find: Sending-end voltage between lines #### **Step 1: Total Impedance per Phase** \[ Z_{total} = 10 \times (0.3 + j0.4) = 3 + j4\,\Omega \] #### **Step 2: Load Current** \[ S = 2500\,kVA = 2,500,000\,VA \] \[ V_{L,R} = 600\,V \] \[ I_{L} = \frac{S}{\sqrt{3} V_{L,R}} = \frac{2,500,000}{\sqrt{3} \times 600} = \frac{2,500,000}{1039.23} = 2,406\,A \] #### **Step 3: Power Factor Angle** \[ \cos\phi = 0.8 \implies \phi = \cos^{-1}(0.8) = 36.87^\circ \] #### **Step 4: Per Phase Current (phasor)** \[ I = 2,406 \angle -36.87^\circ\,A \] #### **Step 5: Per Phase Voltage at Sending End** \[ V_{S,ph} = V_{R,ph} + I Z \] - \( V_{R,ph} = \frac{600}{\sqrt{3}} = 346.41\,V \) \[ I Z = 2,406 \angle -36.87^\circ \times 5 \angle 53.13^\circ \] But \( Z = 3 + j4 = 5 \angle 53.13^\circ \) \[ I Z = 2,406 \times 5 = 12,030 \angle (53.13 - 36.87) = 12,030 \angle 16.26^\circ \] \[ V_{S,ph} = 346.41 \angle 0^\circ + 12,030 \angle 16.26^\circ \] Since \( 346.41 \) is much less than \( 12,030 \), summing as vectors: Let’s resolve both into rectangular form: - \( 346.41 \angle 0^\circ = 346.41 + j0 \) - \( 12,030 \angle 16.26^\circ = 12,030 \times \cos 16.26^\circ + j 12,030 \times \sin 16.26^\circ \) \[ = 11,545 + j3,366 \] Sum: \[ V_{S,ph} = (346.41 + 11,545) + j(0 + 3,366) = 11,891 + j3,366 \] \[ |V_{S,ph}| = \sqrt{11,891^2 + 3,366^2} = \sqrt{141,441,081 + 11,336,756} \approx \sqrt{152,777,837} \approx 12,361\,V \] But this seems off. Let's check our current calculation: **Current re-calculation:** \[ I_L = \frac{2,500,000}{\sqrt{3} \times 600} = 2,406\,A \] But that's a very large current for 600 V. Let's check it: \[ I_L = \frac{2,500,000}{1,039.23} = 2,406\,A \] Correct. Now, line-to-line sending voltage: \[ V_{S,line} = \sqrt{3} \times |V_{S,ph}| = 1.732 \times 12,361 = 21,419\,V \] But this does **not match the answer choices** (8,021 V, 8,210 V, 8,201 V). Let's check if the per-phase voltage should be added algebraically. Given the load voltage is 600 V line-to-line, per phase is 346.41 V. \[ I = 2,406 \angle -36.87^\circ\,A \] \[ Z = 5 \angle 53.13^\circ \] \[ I Z = 2,406 \times 5 = 12,030 \angle 16.26^\circ \] Wait, but the total Z per phase is 3 + j4 = 5 ∠53.13° So, the sending end phase voltage is: \[ V_{S,ph} = V_{R,ph} + I Z \] \[ = 346.41 + 12,030 \angle 16.26^\circ \] But in per-phase, the load voltage is much less than the drop, which is unphysical. But the answer choices suggest the sending voltage is about 8 kV. Given this, the correct calculation would be: \[ I = \frac{2,500,000}{\sqrt{3} \times 600} = 2,406\,A \] Per phase voltage drop: \[ V_{drop,ph} = I \times Z = 2,406 \times 5 = 12,030\,V \] But the load voltage per phase is 346.41 V. So the sending end voltage per phase is: \[ V_{S,ph} = 346.41 + 12,030 = 12,376\,V \] Line-to-line: \[ V_{S,line} = \sqrt{3} \times 12,376 = 21,444\,V \] But this is much higher than the answer choices. Given the much lower numbers in the options, perhaps the load is 2,500 VA (not kVA). Let's check with 2,500 VA: \[ I = \frac{2,500}{\sqrt{3} \times 600} = \frac{2,500}{1,039.23} = 2.406\,A \] Now, \[ V_{drop,ph} = 2.406 \times 5 = 12.03\,V \] Per phase receiving voltage = 346.41 V. \[ V_{S,ph} = 346.41 + 12.03 \angle 16.26^\circ \] \[ 12.03 \cos 16.26^\circ = 11.54 \] \[ 12.03 \sin 16.26^\circ = 3.37 \] \[ (346.41 + 11.54) + j3.37 = 357.95 + j3.37 \] \[ |V_{S,ph}| = \sqrt{357.95^2 + 3.37^2} \approx 358\,V \] Line-to-line: \[ V_{S,line} = \sqrt{3} \times 358 = 619.8\,V \] So the sending voltage is 620 V, just a few volts more than the receiving voltage. But with 2,500 kVA, the answer is 21 kV, which doesn't match the answers. Therefore, **the load should be 2,500 VA, not 2,500 kVA**. So, the answer is **approx 620 V**, but this doesn't match the given choices. But the choices are: - a. 8,021 V - b. 8,210 V - c. 8,201 V Let's try with 25,000 VA: \[ I = \frac{25,000}{1,039.23} = 24.06\,A \] \[ V_{drop,ph} = 24.06 \times 5 = 120.3\,V \] \[ V_{S,ph} = 346.41 + 120.3 \angle 16.26^\circ \] \[ 120.3 \cos 16.26^\circ = 115.45 \] \[ 120.3 \sin 16.26^\circ = 33.67 \] \[ (346.41 + 115.45) + j33.67 = 461.86 + j33.67 \] \[ |V_{S,ph}| = \sqrt{461.86^2 + 33.67^2} \approx 463\,V \] Line-to-line: \[ V_{S,line} = \sqrt{

📢 Instructions:

  • Ask anything relatd to above question only.
  • For new Question goto :

Study Help, Fast Answers

VIPSolutions focuses on clear, step‑by‑step explanations so you can learn quickly. Whether you need an AI‑generated walkthrough or a short hint to get unstuck, each solution is organized for fast reading and easy review later.

Search similar questions, compare approaches, and bookmark the best answers for revision. Our goal is simple: quick, reliable study help that feels natural—not noisy.