Give step-by-step solution with explanation and final answer: What is the minimum ampacity for the secondary conductors of this 4 8 0 V primary / 2 0 8 V secondary transformer? The length of the primary plus secondary conductors is 1 8 feet, it is fed from a feeder tap following the rules in 2 4 0 . 2 1 . Primary OCPD is 1 2 5 amps. Round to the nearest whole number amp.

Question:

Give step-by-step solution with explanation and final answer: What is the minimum ampacity for the secondary conductors of this 4 8 0 V primary / 2 0 8 V secondary transformer? The length of the primary plus secondary conductors is 1 8 feet, it is fed from a feeder tap following the rules in 2 4 0 . 2 1 . Primary OCPD is 1 2 5 amps. Round to the nearest whole number amp.

This is AI generated Response.
Asked by: Test User 100308
Created at: 2025-05-20 06:00:43

Final Answer:

Rendered Raw Text
Did you like this answer?
Let's break down the problem step by step: **Given:** - Transformer: 480V primary / 208V secondary - Length of primary + secondary conductors: 18 feet - This is a **feeder tap** situation, following NEC 240.21(C). - Primary OCPD: 125 amps - Find: **Minimum ampacity for the secondary conductors?** --- ## Step 1: Identify the Relevant NEC Rule This is a transformer secondary tap, so we use **NEC 240.21(C)**. For a **feeder tap**, specifically a **10-foot tap**, the requirements are: - Secondary conductors do **not exceed 10 feet** (ours is 18 feet, so not this one). - For a **25-foot tap** (NEC 240.21(C)(6)): - The secondary conductors **do not exceed 25 feet**. - The ampacity of the secondary conductors is **not less than 1/3 of the rating of the overcurrent device protecting the primary of the transformer** (125A in this case). - The secondary conductors terminate in a single overcurrent protective device or set of fuses that limit the load to that conductor ampacity. Our total length is **18 feet** (less than 25 feet), so the **25-foot tap rule** applies. --- ## Step 2: Calculate Minimum Ampacity **Ampacity must be not less than 1/3 of the rating of the OCPD protecting the primary.** \[ \text{Minimum Ampacity} = \frac{1}{3} \times \text{Primary OCPD} \] \[ = \frac{1}{3} \times 125 \text{A} \] \[ = 41.666... \text{A} \] Round to the nearest whole number: \[ \text{Minimum Ampacity} = 42 \text{A} \] --- ## Step 3: **Final Answer** **The minimum ampacity for the secondary conductors is \(\boxed{42~\text{amps}}\).** --- ### **Summary Table:** | Step | Value | |------|-------------------------------| | Primary OCPD | 125A | | Tap length | 18 feet (under 25-foot rule) | | Fraction required (NEC 240.21(C)(6))| 1/3 | | Calculation | 125A × 1/3 = 41.67A | | Rounded | 42A | **Final Answer:** > **42 amps** is the minimum ampacity required for the secondary conductors.

📢 Instructions:

  • Ask anything relatd to above question only.
  • For new Question goto :

Study Help, Fast Answers

VIPSolutions focuses on clear, step‑by‑step explanations so you can learn quickly. Whether you need an AI‑generated walkthrough or a short hint to get unstuck, each solution is organized for fast reading and easy review later.

Search similar questions, compare approaches, and bookmark the best answers for revision. Our goal is simple: quick, reliable study help that feels natural—not noisy.