Design a condenser that would handle 300 kg/s of steam at 10 kPa and 50 oC and 50 kg/s of drain water at 10 kPa from the low pressure feedwater heater. Seawater, to be used for cooling the condenser, is available at 20 oC. It is recommended to use 90-10 copper-Nickel.
Find in particular:
a- The number of tubes of the condenser
b- the cooling seawater mass flow rate.
c- The pressure drop in the condenser
d- The power attributed to the water flow.
State clearly your assumptions.
Question:
Act like a helpful tutor and exlain me :
Give step-by-step solution with explanation and final answer:
Design a condenser that would handle 300 kg/s of steam at 10 kPa and 50 oC and 50 kg/s of drain water at 10 kPa from the low pressure feedwater heater. Seawater, to be used for cooling the condenser, is available at 20 oC. It is recommended to use 90-10 copper-Nickel.
Find in particular:
a- The number of tubes of the condenser
b- the cooling seawater mass flow rate.
c- The pressure drop in the condenser
d- The power attributed to the water flow.
State clearly your assumptions.
This is AI generated Response.
Asked by: manish kumar
Created at: 2025-09-22 21:38:31
Final Answer:
RenderedRaw Text
Did you like this answer?
# Condenser Design Problem — Step-by-Step Solution
## Given Data
- **Steam mass flow rate (\( \dot{m}_{\text{steam}} \))**: 300 kg/s at 10 kPa, 50°C
- **Drain water mass flow rate (\( \dot{m}_{\text{drain}} \))**: 50 kg/s at 10 kPa
- **Cooling seawater inlet temperature (\( T_{\text{sw,in}} \))**: 20°C
- **Material**: 90-10 copper-nickel
- **All processes at steady state**
---
## Assumptions
1. **Steam condenses at constant pressure (10 kPa)**.
2. **All steam leaves as saturated liquid at 10 kPa**.
3. **Complete condensation (no steam leaves as vapor)**.
4. **Neglect heat losses to surroundings**.
5. **Seawater temperature rise limited to 10°C (common practice, unless otherwise specified)**.
6. **Neglect subcooling of condensate**.
7. **Neglect non-condensables and pressure drop on the shell side**.
8. **Drain water mixes with condensate at 10 kPa**.
---
## Step 1: Find Steam Properties at 10 kPa
From steam tables:
- **At 10 kPa**:
- Saturation temperature, \( T_{\text{sat}} \approx 45.8^\circ\text{C} \)
- Enthalpy of vaporization, \( h_{fg} \approx 2392 \) kJ/kg
- Enthalpy of saturated liquid, \( h_f \approx 191.8 \) kJ/kg
- Enthalpy of saturated vapor, \( h_g \approx 2584 \) kJ/kg
---
## Step 2: Calculate Total Heat to be Removed (\( Q \))
### a) **From Steam Condensation**
\[
Q_{\text{steam}} = \dot{m}_{\text{steam}} \times (h_g - h_f)
\]
\[
Q_{\text{steam}} = 300~\text{kg/s} \times (2584 - 191.8)~\text{kJ/kg}
\]
\[
Q_{\text{steam}} = 300 \times 2392.2 = 717,660~\text{kJ/s} = 717.7~\text{MW}
\]
### b) **From Drain Water Cooling**
Assume drain water at 50°C cooled to 45.8°C (condensate temperature):
\[
Q_{\text{drain}} = \dot{m}_{\text{drain}} \times c_p \times \Delta T
\]
Assume \( c_p = 4.18~\text{kJ/kg} \cdot \text{K} \), \( \Delta T = 50 - 45.8 = 4.2~^\circ\text{C} \):
\[
Q_{\text{drain}} = 50 \times 4.18 \times 4.2 = 877~\text{kJ/s}
\]
### c) **Total Heat Removed**
\[
Q_{\text{total}} = Q_{\text{steam}} + Q_{\text{drain}} \approx 717,660 + 877 = 718,537~\text{kJ/s} = 718.5~\text{MW}
\]
---
## Step 3: Cooling Water Mass Flow Rate (\( \dot{m}_{\text{cw}} \))
Assume seawater temperature rises by \( \Delta T_{\text{cw}} = 10^\circ\text{C} \) (from 20°C to 30°C):
\[
Q_{\text{total}} = \dot{m}_{\text{cw}} \times c_{p,\text{cw}} \times \Delta T_{\text{cw}}
\]
\[
\dot{m}_{\text{cw}} = \frac{Q_{\text{total}}}{c_{p,\text{cw}} \times \Delta T_{\text{cw}}}
\]
Assume \( c_{p,\text{cw}} = 4.18~\text{kJ/kg} \cdot \text{K} \):
\[
\dot{m}_{\text{cw}} = \frac{718,537}{4.18 \times 10} = \frac{718,537}{41.8} \approx 17,191~\text{kg/s}
\]
---
## Step 4: Number of Tubes
Assume:
- Tube inner diameter (\( d_i \)) = 20 mm = 0.02 m
- Tube length (\( L \)) = 8 m
### a) **Velocity of Water in Tubes**
Typical design: \( v = 2~\text{m/s} \)
\[
\dot{m}_{\text{cw}} = \rho \cdot A_{\text{total}} \cdot v
\]
\[
A_{\text{total}} = \frac{\dot{m}_{\text{cw}}}{\rho v}
\]
Seawater \( \rho \approx 1025~\text{kg/m}^3 \):
\[
A_{\text{total}} = \frac{17,191}{1025 \times 2} = \frac{17,191}{2050} \approx 8.39~\text{m}^2
\]
### b) **Area per Tube**
\[
A_{\text{tube}} = \frac{\pi}{4} d_i^2 = \frac{\pi}{4} (0.02)^2 = 3.142 \times 10^{-4}~\text{m}^2
\]
### c) **Number of Tubes**
\[
N_{\text{tubes}} = \frac{A_{\text{total}}}{A_{\text{tube}}} = \frac{8.39}{3.142 \times 10^{-4}} \approx 26,715
\]
---
## Step 5: Pressure Drop in Tubes
For turbulent flow in smooth tubes (Darcy-Weisbach):
\[
\Delta P = f \frac{L}{d} \frac{\rho v^2}{2}
\]
Where:
- \( f \) = friction factor (for turbulent flow, use Blasius equation: \( f = 0.3164/Re^{0.25} \))
- \( L \) = 8 m
- \( d \) = 0.02 m
- \( \rho = 1025~\text{kg/m}^3 \)
- \( v = 2~\text{m/s} \)
### a) **Reynolds Number**
\[
Re = \frac{v d \rho}{\mu}
\]
Assume seawater \( \mu \approx 1.08 \times 10^{-3}~\text{kg/m}\cdot\text{s} \):
\[
Re = \frac{2 \times 0.02 \times 1025}{1.08 \times 10^{-3}} = \frac{41}{1.08 \times 10^{-3}} \approx 37,963
\]
### b) **Friction Factor**
\[
f = 0.3164 / (37,963)^{0.25} \approx 0.021
\]
### c) **Calculate \( \Delta P \)**
\[
\Delta P = 0.021 \times \frac{8}{0.02} \times \frac{1025 \times (2)^2}{2}
\]
\[
= 0.021 \times 400 \times \frac{1025 \times 4}{2}
= 0.021 \times 400 \times 2050
= 0.021 \times 820,000 = 17,220~\text{Pa} = 17.2~\text{kPa}
\]
---
## Step 6: Power Attributed to Water Flow
\[
\text{Power} = \dot{m}_{\text{cw}} \frac{\Delta P}{\rho}
\]
\[
\text{Power} = 17,191~\text{kg/s} \times \frac{17,220~\text{Pa}}{1025~\text{kg/m}^3}
\]
\[
= 17,191 \times 16.8 = 288,815~\text{W} \approx 289~\text{kW}
\]
---
## **Summary Table**
| **Quantity** | **Value** |
|-------------------------------------|-----------------------|
| Number of tubes (\(N_{\text{tubes}}\)) | ~26,700 (rounded) |
| Cooling water mass flow (\(\dot{m}_{\text{cw}}\)) | ~17,200 kg/s |
| Pressure drop (\(\Delta P\)) | ~17.2 kPa |
| Power for water flow | ~289 kW |
---
## **Final Answers**
### a. **Number of tubes of the condenser**
**~26,700 tubes** (assuming 20 mm diameter, 8 m length, 2 m/s velocity)
### b. **Cooling seawater mass flow rate**
**~17,200 kg/s**
### c. **Pressure drop in the condenser**
**~17.2 kPa**
### d. **Power attributed to the water flow**
**~289 kW**
---
## **Notes on Assumptions**
- If tube diameter/length or seawater temperature rise differ, update calculations accordingly.
- Tube material (90-10 Cu-Ni) is suitable for seawater; actual design needs corrosion and fouling factors.
- Calculations are first approximations for preliminary design.
---
**If you need further breakdown of any specific step or want to adjust assumptions, let me know!**