A
3
phase
5
0
Hz
,
3
2
km of the transmission line having resistance
0
.
0
7
5
/
km
,
2
.
4
cm outside diameter and spaced equilaterally
2
meters between them. The line deliveing
2
6
MW at a power factor of
0
.
8
2
lagging with
4
1
kV
.
Determine
(
a
)
Sending end voltage,
(
b
)
Voltage regulation
(
c
)
Efficiency of line using nominal it method
Question:
A
3
phase
5
0
Hz
,
3
2
km of the transmission line having resistance
0
.
0
7
5
/
km
,
2
.
4
cm outside diameter and spaced equilaterally
2
meters between them. The line deliveing
2
6
MW at a power factor of
0
.
8
2
lagging with
4
1
kV
.
Determine
(
a
)
Sending end voltage,
(
b
)
Voltage regulation
(
c
)
Efficiency of line using nominal it method
This is AI generated Response.
Asked by: Jack
Created at: 2025-10-12 18:04:54
Final Answer:
RenderedRaw Text
Did you like this answer?
# Transmission Line Calculation (Nominal π Method)
Given:
- **Length of line, \( l \)**: 32 km
- **Resistance per km, \( R \)**: .075 Ω/km
- **Outside diameter of conductor, \( d \)**: 2.4 cm = .024 m
- **Spacing between conductors, \( D \)**: 2 m
- **Frequency, \( f \)**: 50 Hz
- **Load delivered, \( P \)**: 26 MW
- **Line-to-line voltage at receiving end, \( V_R \)**: 41 kV
- **Power factor, \( pf \)**: .82 lagging
- **System**: 3-phase
---
## Step 1: Calculate Line Parameters
### 1. Total Resistance (\( R \))
\[
R_{total} = R \times l = .075 \times 32 = 2.4\ \Omega
\]
### 2. Inductance per Phase per km (\( L \))
\[
L = 2 \times 10^{-7} \ln\left(\frac{D}{r'}\right) \quad \text{(H/m)}
\]
where \( r' = .7788r \), and \( r = \frac{d}{2} = .012 \) m.
\[
r' = .7788 \times .012 = .0093456\ \text{m}
\]
\[
L = 2 \times 10^{-7} \ln\left(\frac{2}{.0093456}\right) = 2 \times 10^{-7} \ln(214.14)
\]
\[
\ln(214.14) \approx 5.366
\]
\[
L = 2 \times 10^{-7} \times 5.366 = 1.073 \times 10^{-6}\ \text{H/m}
\]
\[
L_\text{per km} = 1.073 \times 10^{-6} \times 100 = 1.073 \times 10^{-3}\ \text{H/km}
\]
\[
L_{total} = 1.073 \times 10^{-3} \times 32 = .03434\ \text{H}
\]
### 3. Capacitance per Phase per km (\( C \))
\[
C = \frac{2\pi \varepsilon}{\ln(D/r')}
\]
where \( \varepsilon = 8.854 \times 10^{-12}\ \text{F/m} \).
\[
C = \frac{2\pi \times 8.854 \times 10^{-12}}{5.366} = \frac{5.564 \times 10^{-11}}{5.366} = 1.037 \times 10^{-11}\ \text{F/m}
\]
\[
C_\text{per km} = 1.037 \times 10^{-11} \times 100 = 1.037 \times 10^{-8} \ \text{F/km}
\]
\[
C_{total} = 1.037 \times 10^{-8} \times 32 = 3.318 \times 10^{-7} \ \text{F}
\]
---
## Step 2: Load Current
\[
\text{Apparent Power } S = \frac{P}{pf} = \frac{26 \times 10^6}{.82} = 31.71 \times 10^6 \text{ VA}
\]
\[
I_R = \frac{S}{\sqrt{3} V_R} = \frac{31.71 \times 10^6}{\sqrt{3} \times 41 \times 10^3}
\]
\[
I_R = \frac{31.71 \times 10^6}{71,009.4} = 446.4\ \text{A}
\]
---
## Step 3: Nominal π Model Parameters
### Series Impedance per phase
\[
Z = R_{total} + j \omega L_{total}
\]
\[
\omega = 2\pi f = 314.16 \text{ rad/s}
\]
\[
j \omega L_{total} = j \times 314.16 \times .03434 = j 10.79
\]
\[
Z = 2.4 + j 10.79\ \Omega
\]
### Shunt Admittance per phase
\[
Y = j \omega C_{total}
\]
\[
Y = j \times 314.16 \times 3.318 \times 10^{-7} = j .0001043
\]
---
## Step 4: Nominal π ABCD Parameters
\[
A = D = 1 + \frac{YZ}{2}
\]
\[
B = Z
\]
\[
C = Y \left[1 + \frac{YZ}{4}\right]
\]
First, calculate \( YZ \):
\[
YZ = (j .0001043) \times (2.4 + j10.79)
= j .0001043 \times 2.4 + j .0001043 \times j 10.79
= j .0002503 - .001126
\]
\[
A = 1 + \frac{YZ}{2} = 1 + \frac{-.001126 + j .0002503}{2}
= 1 - .000563 + j .000125
= .99944 + j .000125
\]
---
## Step 5: Receiving End Per Phase Values
\[
V_{R,\text{phase}} = \frac{41,000}{\sqrt{3}} = 23,677\ \text{V}
\]
\[
I_R = 446.4\ \text{A}
\]
\[
\text{Phase angle} = \cos^{-1}(.82) = 34.9^\circ
\]
\[
I_R = 446.4 \angle -34.9^\circ\ \text{A}
\]
---
## Step 6: Sending End Voltage (Per Phase)
\[
V_S = A V_R + B I_R
\]
With
- \( V_R = 23,677 \angle ^\circ \) V
- \( I_R = 446.4 \angle -34.9^\circ \) A
- \( B = 2.4 + j10.79 = 11.06 \angle 77.45^\circ \) Ω
Calculate \( B I_R \):
\[
|B I_R| = 11.06 \times 446.4 = 4,936.8
\]
\[
\text{Angle} = 77.45^\circ + (-34.9^\circ) = 42.55^\circ
\]
\[
B I_R = 4,936.8 \angle 42.55^\circ
\]
Now, \( A V_R \approx .99944 \times 23,677 = 23,663 \)
(Due to small imaginary part, phase shift is negligible.)
Sum using rectangular form:
- \( A V_R \approx 23,663 + j 2.96 \) V
- \( B I_R = 4,936.8 \cos 42.55^\circ + j 4,936.8 \sin 42.55^\circ \)
- \( = 4,936.8 \times .7368 = 3,637.6 \)
- \( = 4,936.8 \times .6761 = 3,340.7 \)
- So, \( B I_R \approx 3,637.6 + j 3,340.7 \) V
Add:
\[
V_S = (23,663 + 3,637.6) + j (2.96 + 3,340.7) = 27,300.6 + j 3,343.7
\]
\[
|V_S| = \sqrt{27,300.6^2 + 3,343.7^2} = \sqrt{745,312,000 + 11,185,300} = \sqrt{756,497,300}
= 27,509\ \text{V}
\]
Per phase, so total line-to-line:
\[
V_{S,LL} = 27,509 \times \sqrt{3} = 47,646\ \text{V}
\]
**(a) Sending end voltage = \(\boxed{47.65\ \text{kV}}\) (line-to-line)**
---
## Step 7: Voltage Regulation
\[
\text{Regulation} = \frac{V_{S,LL} - V_{R,LL}}{V_{R,LL}} \times 100\%
= \frac{47,646 - 41,000}{41,000} \times 100 = 16.2\%
\]
**(b) Voltage Regulation = \(\boxed{16.2\%}\)**
---
## Step 8: Efficiency
\[
\text{Sending end apparent power} =
\sqrt{3} \times V_{S,LL} \times I_S
\]
First, compute sending end current (\( I_S \)):
\[
I_S = A I_R + C V_R
\]
But since shunt admittance is small, \( I_S \approx I_R \), so:
\[
\text{Sending end real power} =
\sqrt{3} \times V_{S,LL} \times I_R \times \text{pf}_S
\]
Estimate \( pf_S \approx .82 \) (since losses are relatively small):
\[
P_S \approx \sqrt{3} \times 47,646 \times 446.4 \times .82 = 28,374,000\ \text{W} = 28.37\ \text{MW}
\]
\[
\text{Efficiency} = \frac{P_{load}}{P_S} \times 100
= \frac{26}{28.37} \times 100 = 91.7\%
\]
**(c) Efficiency = \(\boxed{91.7\%}\)**
---
# **Summary Table**
| Quantity | Value |
|-------------------------|-----------|
| Sending End Voltage | 47.65 kV (L-L) |
| Voltage Regulation | 16.2% |
| Efficiency | 91.7% |
---
## **Assumptions and Approximations**
- Calculations are per phase, then converted to line-to-line where needed.
- Some small effects (e.g., shunt admittance at sending end) are neglected for simplicity.
- If you need three-phase phasor diagrams or more detailed steps, let me know.